Introduction: A 12.8V 30Ah LiFePO4 module gives UPS and small solar backup projects a compact 384Wh building block, and the customization decision starts with load, charging, terminal, and installation conditions.
A 384Wh low-voltage module can carry more backup duty than its size suggests once the load, charging, and terminal conditions are pinned down. A backup design gets safer when the load in watts, required runtime, charger, and available cabinet space are written down first. The Surlon Power 12.8V 30Ah LiFePO4 pack provides 384Wh in a compact 2.8 kg block with a built-in BMS, IP65 ABS enclosure, and M8 metal bolt terminals. That capacity can support a controller, communications link, small inverter, or a few lights through an outage, provided the continuous load stays within the 20A limit. The main decision is whether one module or several fit the project, and which terminal, BMS, or enclosure details need confirmation before you order.
Start with the load, not the datasheet headline. The module stores 384Wh and delivers up to 20A continuously; at 12.8V, 20A is roughly 256W. Below that ceiling, runtime math is straightforward: usable watt-hours divided by load watts. A 100W monitoring and communications load draws about 8A and would run for roughly 3.8 hours at full 384Wh; after a 90% efficient DC-DC converter and a practical depth of discharge, plan on about two and a half hours. A 60W overnight load stretches further, which makes this pack a fit for small solar sites with steady, modest demand rather than spiky loads. Above roughly 250W, the current limit becomes the binding constraint before the energy does. A 500W inverter load pulls about 40A at 12.8V, so one module is not enough. Two modules in parallel share current and double stored energy; series arrangements for a 24V or 48V bus change the BMS requirements and need project review. Plan the physical layout at the same time. Each pack measures 152 × 100 × 131 mm (±2 mm) and weighs about 2.8 kg, so a cabinet that held a 12V SLA battery may have room, but bracket space, cable bend radius, and service access need to be checked against the drawing before the enclosure is cut.
The standard configuration already covers much of the integration work: M8 metal bolt terminals, an ABS enclosure rated IP65, and an optional LED state-of-charge indicator. Projects that need a different configuration usually focus on four items.
Treat these as one package. A terminal change changes cable stress, a BMS current limit changes the acceptable load, and a mounting change affects how much heat the pack sees. When a project moves beyond the standard 12.8V 30Ah 384Wh configuration, work from your drawing and load profile. A lithium battery pack manufacturer can review terminal, BMS, and enclosure changes together and provide a sample pack to confirm fit before production.
The pack charges on a CC/CV profile at 14.4 ± 0.2V, with a 14.6 ± 0.2V charge cut-off, a recommended charge current of 6A, and a 30A maximum. Those values shape how the rest of the system should be configured. In a small off-grid solar setup, the MPPT controller needs a LiFePO4 charge profile with the absorption voltage set inside that window and equalization or desulfation stages switched off. A lead-acid profile left in place may undercharge the pack or drive it into protection. On the UPS side, check the float and boost voltages of the rectifier or internal charger and confirm that temperature compensation is disabled or set for lithium. Temperature limits shape where the pack can live. Charging is rated from 0°C to 45°C, discharging from -20°C to 60°C, and storage from 0°C to 40°C. A sealed outdoor cabinet in direct summer sun can sit well above ambient, so shade, airflow, and mounting height matter as much as the IP65 rating. Below freezing, the pack can still discharge but should not be charged, which is relevant for unheated solar sites in winter. Also plan the low-voltage side: the discharge cut-off is 10V, and a system that keeps pulling below that point will trip protection. Surlon Power reviews charger settings and cabinet layout before shipment so a protection trip does not appear at commissioning.
A 12.8V 30Ah pack is a practical building block: 384Wh, 20A continuous, 14.4V charging, M8 terminals, and an IP65 ABS case. Its engineering value comes from matching it to a defined load, a compatible charger, and a real cabinet. Before requesting pricing, put the essentials on one page: continuous and peak load, required runtime, DC bus voltage, charger output and profile, terminal type, available space, ambient temperature, and quantity. Use those details to ask a lithium battery supplier for a project-specific quote. Surlon Power can then confirm whether the standard 12.8V 30Ah LiFePO4 battery fits, or whether a custom LiFePO4 battery with different terminals, BMS thresholds, or enclosure details is the better route. Price, MOQ, lead time, and the documentation set for your destination market are confirmed in writing for the specific project.
A: Send the load in watts or amps, the runtime you need during an outage, the DC bus voltage, the charger or rectifier output and charge profile, the terminal or connector type, the available cabinet space, ambient temperature, estimated quantity, and the destination market. With those details, a supplier can quote the right configuration instead of a generic pack.
A: Yes. The standard build uses M8 metal bolt terminals, and other terminal or connector arrangements can be reviewed against your drawing. BMS protection thresholds and current limits can be aligned with your charger and load profile, and enclosure or state-of-charge indicator options are part of the same review. A sample pack can confirm the fit before production.
A: Add up daily watt-hours for the equipment you need to keep running, decide how many hours or days of autonomy the site requires, and divide by usable energy per module at a realistic depth of discharge. Keep continuous draw under about 250W per pack, add modules in parallel for larger loads, and confirm that your charge controller can refill the pack within the solar window.